Specifying MV Switchgear: Key Ratings Explained

Why rated voltage, current, short-circuit, insulation and internal arc ratings must be read together when specifying MV switchgear.

A switchgear panel can carry its normal load current for decades without incident, yet the moment that matters most is the fraction of a second when a fault occurs. Will the busbars hold together under electromagnetic forces? Will the circuit-breaker interrupt the current? If an internal arc occurs, will people standing nearby be protected? A datasheet answers these questions through a set of ratings, and each rating covers a different part of the problem.

This article answers a practical question: which ratings define medium-voltage (MV) switchgear, what does each one protect against, and why must they be evaluated together rather than one at a time?

Key takeaways

  • Rated voltage is the maximum system voltage the equipment is designed for — it is not the nominal system voltage, and it is normally higher.
  • Rated normal current describes continuous operation; short-time, peak, breaking and making ratings describe fault conditions. Both must be specified.
  • Short-circuit ratings must be derived from a network fault study for the actual installation point, not assumed.
  • Insulation levels (power-frequency and lightning impulse withstand) follow from the rated voltage but may need review for altitude and exposure.
  • Internal arc classification (IAC) is about personnel safety, and it is only valid for the accessibility type, sides and installation conditions under which it was tested.
  • No single rating is meaningful in isolation: a panel is only as capable as its weakest relevant rating at the point of installation.

Understanding the key ratings

Standards framework: the IEC 62271 series

Most MV switchgear supplied internationally is designed and tested to the IEC 62271 series. At the level of what each part governs:

StandardWhat it coversWhy it matters
IEC 62271-1Common specifications for alternating current switchgear and controlgear — defines rated characteristics, standard values and common test requirements used by the other parts.Sets the rating values and tests referred to throughout a switchgear specification
IEC 62271-100Alternating current circuit-breakers.Applies to circuit-breaker functions, such as incomers and feeders that must interrupt fault current
IEC 62271-102Alternating current disconnectors and earthing switches.Covers the isolating and earthing functions that make maintenance safe
IEC 62271-103Switches for rated voltages above 1 kV up to and including 52 kV.Applies to load-break switches, such as the ring switches in RMUs
IEC 62271-105Alternating current switch-fuse combinations.Applies to fused switch functions, commonly used to protect distribution transformers
IEC 62271-200AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV.The assembly-level standard for the switchboard as a whole, including internal arc classification
IEC 62271-202High-voltage/low-voltage prefabricated substations.Relevant when the switchgear forms part of a compact / package substation

A switchgear assembly is therefore assessed at two levels: the assembly (for example to IEC 62271-200) and the devices inside it (circuit-breakers, switches, earthing switches, fuse combinations, each to its own part). A specification should refer to both. Edition years matter; the applicable editions should be confirmed for each project.

Metal-enclosed MV switchgear panel: main compartments and parts Conceptual side-section of one generic metal-enclosed medium-voltage switchgear panel (IEC 62271-200 style), front on the left and rear on the right, with eight numbered parts. 1: low-voltage relay and instrument compartment at the front top, holding the protection relay, meters and controls, segregated from the MV parts. 2: busbar compartment at the top rear, with the main busbars that run across the line-up. 3: switching-device compartment in the centre with a withdrawable circuit-breaker (or a switch, depending on the panel function). 4: cable-termination compartment at the bottom with the incoming or outgoing MV cable termination. 5: current and voltage transformers on the main circuit. 6: earthing switch in the cable compartment. 7: pressure-relief flap and arc-gas exhaust duct at the top of the enclosure. 8: the metal enclosure and internal metallic partitions. The main circuit runs from the busbars down through the circuit-breaker to the cable termination. Illustrative only, not a product drawing. Metal-enclosed MV switchgear panel: main compartments Generic arrangement, side section (IEC 62271-200 style). Front = operator side. Arc-gas exhaust duct 7 8 Relay Meters, controls 1 Main busbars 2 Circuit-breaker (withdrawable) 3 CT VT 5 6 4 FRONT (operator side) REAR Legend 1 Low-voltage compartment Protection relay, meters and controls; front of panel, segregated from MV parts. 2 Busbar compartment Main busbars at the top, running across the switchgear line-up. 3 Switching-device compartment Withdrawable circuit-breaker, or a switch, according to the panel function. 4 Cable-termination compartment Incoming / outgoing MV cable terminations at the bottom. 5 Current & voltage transformers (CT/VT) Instrument transformers on the main circuit. 6 Earthing switch Located in the cable compartment. 7 Pressure-relief flap / arc-gas exhaust duct At the top of the enclosure. 8 Metal enclosure & internal partitions Outer frame and internal metallic partitions between compartments. Conceptual / illustrative — not a product drawing. Generic metal-enclosed arrangement · IEC 62271-200 style
Generic metal-enclosed MV switchgear panel: LV, busbar, switching-device and cable compartments, CT/VT, earthing switch and arc-gas exhaust.

Rated voltage (Ur) vs system voltage

The nominal system voltage is the voltage by which a network is identified (for example 11 kV, 20 kV or 33 kV). The rated voltage (Ur) of switchgear is the maximum system voltage for which the equipment is designed. IEC standard rated voltages within the scope of AdepaTrade’s supply include values such as 7.2, 12, 17.5, 24 and 36 kV.

Standard values from IEC 60038, Table 3, Series I (50 Hz and 60 Hz systems). Confirm the rated voltage against the network operator’s requirements:

Nominal system voltageHighest voltage for equipment (typical switchgear rated voltage)
6.6 kV or 6 kV7.2 kV
11 kV or 10 kV12 kV
15 kV (non-preferred)17.5 kV
22 kV or 20 kV24 kV
33 kV or 30 kV36 kV

The two nominal values in a row are alternatives; IEC 60038 recommends that only one of them is used in any one country, and it shows 15 kV and 17.5 kV as non-preferred values. 13.8 kV is not a Series I value: IEC 60038 lists it in Series II (60 Hz systems, mainly North American practice), with a highest voltage for equipment of 14.52 kV. Because equipment may only be used on systems whose highest voltage does not exceed its highest voltage for equipment, 17.5 kV IEC-rated switchgear meets this condition on a 13.8 kV network. The rated voltage is still a selection to agree with the network operator.

The common error is to specify “11 kV switchgear” without stating the rated voltage, or to assume the next rating up automatically covers local practice. Some networks operate close to the upper limit of a rating band, and some utilities mandate a specific rated voltage regardless of nominal voltage.

Rated normal current (Ir)

The rated normal current is the r.m.s. current the equipment can carry continuously under specified service conditions without exceeding permitted temperature rises. It applies separately to busbars and to each functional unit (incomer, feeder, transformer feeder, bus coupler).

Important points:

  • It is defined at stated ambient conditions. Higher ambient temperature, poor ventilation of the switchroom or enclosure, or installation inside a kiosk can reduce the current the equipment can actually carry. Derating information is manufacturer-specific.
  • Busbar rating should reflect the total current that can flow along the busbar, including future feeders and possible reconfigurations — not just the largest single feeder.
  • Normal current says nothing about fault capability. A 630 A panel and a 1250 A panel may have the same, or different, short-circuit ratings.

Short-time withstand current (Ik) and rated duration (tk)

The rated short-time withstand current (Ik) is the r.m.s. current the equipment can carry in the closed position for a specified rated duration of short circuit (tk) without damage. It is a thermal rating: it tests whether conductors, joints and contacts survive the heating caused by fault current until protection clears the fault.

Ik must always be stated together with its duration, for example “20 kA for 1 s” or “25 kA for 3 s”. A rating of “25 kA” without a duration is incomplete. The duration selected must be consistent with the total fault clearance time of the upstream protection, including relay time, breaker operating time and any intentional grading delays.

Peak withstand current (Ip)

The rated peak withstand current (Ip) is the highest instantaneous current the equipment must withstand in the closed position — typically occurring in the first major loop of an asymmetrical fault. It is a mechanical rating: it tests whether busbars, supports and contacts survive the electromagnetic forces.

IEC 62271-1 relates Ip to Ik through a factor that depends on the system frequency and the DC time constant of the network. For the standard time constant, the commonly used factors are 2.5 × Ik at 50 Hz and 2.6 × Ik at 60 Hz (for example, 25 kA Ik corresponds to 62.5 kA Ip at 50 Hz). Networks with a higher X/R ratio — for example close to large generators or transformers — may require a higher factor; this must be confirmed by the network study.

MV switchgear current ratings: normal current versus fault ratings Schematic current-versus-time graph (time not to scale, amplitudes illustrative). A low continuous band shows the rated normal current Ir, a continuous thermal rating governed by temperature rise. At fault inception an asymmetrical, decaying AC fault current appears: its first major peak is the rated peak withstand current Ip, a mechanical rating for electromagnetic forces; the symmetrical r.m.s. level is the rated short-time withstand current Ik, a thermal rating for fault heating; and a brace along the fault shows the rated duration tk, for example 1 s or 3 s. A callout states Ip = 2.5 × Ik at 50 Hz and 2.6 × Ik at 60 Hz (standard time constant), with the example Ik = 25 kA giving Ip = 62.5 kA at 50 Hz; a muted note in the callout clarifies that these are standardized rating-convention factors (IEC standard time constant), not a universal physical relationship for every fault condition. A note says Ik and tk must be stated together and both derive from the network fault study and protection clearance time. MV switchgear: normal current vs fault ratings Schematic current–time graph · time axis not to scale · amplitudes illustrative Time (not to scale) Current 0 fault cleared Ip Rated peak withstand current (Ip) — mechanical (electromagnetic force) Ik (r.m.s.) Rated short-time withstand current (Ik) — thermal (fault heating) Rated normal current (Ir) — continuous, thermal (temperature rise) Ir Rated duration tk (e.g. 1 s or 3 s) Ip = 2.5 × Ik at 50 Hz · 2.6 × Ik at 60 Hz (standard time constant) Example: Ik = 25 kA → Ip = 62.5 kA (50 Hz) Standardized rating-convention factors (IEC standard time constant) — not a universal physical relationship for every fault condition. Ik and tk must be stated together; both derive from the network fault study and protection clearance time.
Rated normal current Ir is a continuous thermal rating; fault ratings Ip (peak, mechanical) and Ik for duration tk (thermal) are separate.

Short-circuit breaking and making duties

These apply to switching devices, and the device type matters:

  • Circuit-breakers have a rated short-circuit breaking current (Isc), the highest fault current they can interrupt, and a rated short-circuit making current, the peak current they can close onto (normally equal in value to Ip). Breakers also have a defined operating sequence (for example open – delay – close/open – delay – close/open) that matters where auto-reclosing is used.
  • Load-break switches are designed to make and break normal load currents. They usually have a short-circuit making capability (so they can be safely closed onto a fault) but are not designed to break short-circuit current.
  • Switch-fuse combinations rely on fuses to interrupt fault current; the switch, striker and fuse together define the combination’s performance.
  • Earthing switches may have a short-circuit making capability so that accidental closing onto a live circuit does not cause failure.

A common gap is to specify “25 kA” for a ring main unit without distinguishing which functions carry, make or break that current.

Insulation levels: rated withstand voltages

Insulation level is expressed as two values:

  • Rated short-duration power-frequency withstand voltage (Ud) — represents temporary overvoltages at system frequency.
  • Rated lightning impulse withstand voltage (Up) — represents fast transient overvoltages caused by lightning.

IEC 62271-1 associates standard insulation levels with each rated voltage. Typical values (illustrative, common-value list; confirm the applicable table and any national alternatives):

Rated voltage UrTypical Ud (1 min, r.m.s.)Typical Up (peak)
12 kV28 kV75 kV
24 kV50 kV125 kV
36 kV70 kV170 kV

Two practical points:

  • Altitude. Air is a weaker insulator at higher altitude. Standard ratings normally assume installation up to 1000 m above sea level; above that, air-insulated parts may require correction or a higher insulation level. Gas-insulated sections are affected differently. The correction method and its applicability must be confirmed with the manufacturer.
  • Exposure. Equipment connected to overhead lines is more exposed to lightning surges; surge arresters and insulation coordination (IEC 60071 series) should be considered at the system level.

Internal arc classification (IAC)

An internal arc is a fault inside the switchgear enclosure that releases large amounts of energy, hot gases and pressure. Internal arc classification, tested under IEC 62271-200, demonstrates that the enclosure protects persons in the vicinity under defined conditions. It does not mean the equipment remains undamaged or in service.

An IAC designation contains:

  • Accessibility type: type A — accessible to authorised personnel only; type B — unrestricted accessibility, including the general public; type C — accessibility restricted by installation out of reach (for example pole-mounted).
  • Accessible sides: F (front), L (lateral), R (rear).
  • Arc fault current and duration, for example 16 kA for 1 s.

A designation such as IAC AFLR 20 kA 1 s therefore means: tested for authorised-personnel access, with front, lateral and rear sides accessible, at 20 kA for 1 s.

Internal Arc Classification (IAC): accessible sides and how to read the designation Conceptual diagram of Internal Arc Classification. On the left, a plan view of an enclosed switchgear line-up marks the three accessible sides: F = front, L = lateral (side) and R = rear, with an internal arc inside one panel. Below it, a side section shows the arc inside the enclosure, arc gases released upward through an exhaust duct away from the operator, and an operator standing at the front protected by the enclosure. On the right, the designation IAC AFLR 20 kA 1 s is decoded: IAC is Internal Arc Classification, a personnel-safety classification under which the enclosure may still be damaged or out of service; A is the accessibility type (A = authorised personnel only, B = unrestricted including the public, C = out of reach, e.g. pole-mounted); FLR are the accessible sides (front, lateral, rear); 20 kA is the arc fault current and 1 s the duration. Note: valid only as tested — room size, ceiling height and arc-gas exhaust must match the tested arrangement. Internal Arc Classification (IAC) Accessible sides, accessibility types and how to read the designation Plan view — accessible sides R = Rear F = Front L = Lateral (side) internal arc Side section — arc gas vented away from the operator internal arc Arc gases exhausted upward / away FRONT Operator at front, protected by the enclosure Reading the designation IAC AFLR 20 kA 1 s IAC Internal Arc Classification — personnel safety; the enclosure may still be damaged / out of service. A Accessibility type: A = authorised personnel only · B = unrestricted (incl. public) · C = out of reach (e.g. pole-mounted). FLR Accessible sides: F front · L lateral · R rear. 20 kA Arc fault current. 1 s Duration of the arc fault. Valid only as tested — room size, ceiling height and arc-gas exhaust must match the tested arrangement. Conceptual / illustrative — not a product drawing.
Reading an IAC designation: accessible sides F/L/R, accessibility type A/B/C, arc fault current and duration — e.g. IAC AFLR 20 kA 1 s.

Interpretation points:

  • The classification is valid only when installed as tested — including room dimensions, ceiling height and arc gas exhaust arrangements (ducts, absorbers or venting routes). A wall-mounted installation of a panel classified for rear access, or a missing exhaust duct, can invalidate the assumption.
  • The arc fault current is often lower than, or equal to, the short-time withstand current. It should be compared with the actual prospective fault current.
  • Other classifications under IEC 62271-200, such as loss of service continuity (LSC) and partition class, describe maintenance and operational continuity rather than arc safety. They are different properties and should be specified separately.

Service conditions

All ratings are valid only under the service conditions defined by the standard or agreed with the manufacturer. IEC 62271-1 defines “normal” indoor and outdoor service conditions, covering ambient temperature range, altitude, humidity, pollution and condensation. Typical normal indoor assumptions include an upper ambient air temperature of 40 °C, a limited 24-hour average, and altitude up to 1000 m — the exact limits must be checked in the applicable edition.

Projects in hot climates, at high altitude, in coastal or desert environments, or with high humidity and condensation risk should state special service conditions explicitly so the manufacturer can confirm derating, insulation correction or design adjustments.

Why ratings must be evaluated together

RatingSymbol / unitWhat it protects againstDepends on
Rated voltageUr, kVInsulation stress at maximum system voltageNetwork nominal voltage and operating range
Rated normal currentIr, AOverheating in continuous serviceLoad, busbar topology, ambient, enclosure
Short-time withstand currentIk, kA (r.m.s.) with tk, sThermal damage during a faultProspective fault level and clearance time
Peak withstand currentIp, kA (peak)Mechanical forces during the first fault peakIk, frequency, network X/R
Short-circuit breaking currentIsc, kA (r.m.s.)Failure to interrupt a faultDevice type and fault level
Short-circuit making currentkA (peak)Failure when closing onto a faultNormally equals Ip
Power-frequency withstandUd, kV (r.m.s.)Temporary overvoltagesUr, altitude
Lightning impulse withstandUp, kV (peak)Transient overvoltagesUr, exposure, altitude, surge protection
Internal arc classificationIAC type, sides, kA, sInjury to persons from internal arcAccessibility, installation, exhaust, fault level

These ratings interact:

  • A high Ik is ineffective if the rated duration is shorter than the actual fault clearance time.
  • Ik and Ip must be consistent with each other and with the network X/R ratio.
  • A breaker’s breaking capacity must match or exceed the busbar fault level — but load-break switches in the same line-up are not expected to break faults, so protection philosophy must assign that duty correctly.
  • IAC ratings are linked to the fault current and the room design; a high Ik with a low arc rating may leave an operator safety gap.
  • Every rating is conditional on service conditions; a derating for temperature or altitude can change the outcome of the comparison.

Practical selection guidance

  1. Start with the network study. Obtain the maximum prospective fault current (r.m.s. and peak) at the installation point, including future network reinforcement and any embedded generation.
  2. Define the rated voltage and insulation level from the network operator’s requirements, adjusting for altitude and exposure where relevant.
  3. Size normal currents for busbars and each functional unit, including planned expansion and ambient derating.
  4. Match Ik and tk to the protection scheme — confirm total clearance time and any backup protection time.
  5. Assign switching duties per function: which units need circuit-breakers, which can use switches or switch-fuse combinations.
  6. Specify IAC fully: accessibility type, sides, current and duration — and describe the room or enclosure so the manufacturer can confirm arc gas management.
  7. State service conditions explicitly where they depart from normal conditions.
  8. Request evidence: type test reports for the specific design and ratings, and routine test documentation for the supplied units.

Common mistakes and specification gaps

  • Specifying nominal system voltage instead of rated voltage.
  • Giving a short-circuit rating without the rated duration, or without the peak value.
  • Assuming a load-break switch can interrupt short-circuit current.
  • Selecting fault ratings from typical values rather than a project-specific fault study.
  • Ignoring future fault level increases when the network is reinforced or generation is added.
  • Specifying IAC without accessibility type and sides, or installing the switchgear in a way that does not match the tested arrangement (wall clearance, ceiling height, exhaust route).
  • Omitting altitude, high ambient temperature or pollution conditions.
  • Accepting type test evidence for a different rating, configuration or variant than the one being supplied.
  • Referring to “IEC 62271” generally without stating which parts and editions apply.